另类视频网站|日韩激情不卡视频|国产爆乳精品免费观看一牛影视|久久人妻精品秘书丝袜激

  • Golden Samurai TD31-6kVA
< >
  • Golden Samurai TD31-6kVA

Golden Samurai TD31-6kVA

product power:4.8KW(千瓦)

product capacity:6KVA 【View products of the same capacity】

series:Power frequency TD series 【View the same series of products】

voltage input and output:Three-in-single-out (380V:220V)

weight:58 kg( 公斤)

size(LWH):260*560*717 MM(毫米)17U

Shape classification:

  • Product Overview
  • For details
  • Installation Notes
  • Product Image
  • After-sales service
  • Documentation
  • 1. Advanced DSP digital control technology

    Adopt advanced digital control technology to improve the stability and reliability of the machine. The ECO function maximizes the cost savings for customers.

    2. Large screen LCD+LED display in Chinese and English

    Perfect combination, display in Chinese and English, can display the content of input, output, battery voltage, load status, current, UPS working status and mode, temperature, model manufacturer number. Main parameters such as voltage, frequency, current, etc. of the machine can be set directly through the LCD display

    3. Dual AC power input

    The main AC input power and bypass AC input power can use two sets of inputs from different power grids. LCD+LED

    4. Generator mode

    Support generator input

    5. Parallel function

    8 UPSs are connected in parallel for redundancy.

    6. Strong load capacity

    It adopts full-bridge topology with output isolation transformer, which has stronger load capacity and impact resistance. And optional bypass output isolation transformer.

    7. Full-bridge inverter architecture:

    UPS adopts advanced DSP design, three-phase independent full-bridge inverter system design, its output voltage and phase are completely unaffected by three-phase unbalanced load, and can withstand 100% unbalanced load.

    8. The charging current can be set

    The user can freely set an appropriate charging current (1~50A) on the LCD according to the battery capacity. When the UPS is running at full load, the maximum charging current is 50A.

    9. Battery management function

    Mainly include battery failure detection, low battery, battery loss and other conventional functions.

    10. Frequency and phase sequence adaptive system

    50Hz or 60Hz;

    The output phase sequence can automatically track and lock according to the input phase sequence.

    11. Protection and alarm functions

    LCD, output contacts, etc. prompt in time, self-diagnosis function at startup; with protection functions such as overload protection, output short circuit, input overvoltage, lightning protection, and battery reverse connection.

    12. Powerful panel setting function

    Output voltage: 200/208/220/230/240Vac (phase voltage)

    Output frequency: 50Hz/60Hz

    Charging current: 1~50A

    Battery discharge time

    Timing boot

    Shutdown timer

    Working mode: ECO, EPO

    LCD Chinese and English setting input frequency: 40~70Hz

    It has a variety of alarm methods, which can be automatically set according to the mains frequency through sound, light, and output frequency.

    13. EPO emergency shutdown function

    Through the "Emergency Stop" button, the rectifier and inverter can be turned off, and the output (including bypass and inverter) can be blocked. This button can be used when an emergency occurs or cannot be shut down normally.

    14. Host monitoring and alarm function

    15. Smart slot expandability function (optional)

    You can choose USB card, AS400 card, CMC monitoring card, SNMP card, RS485 card, EMD environmental monitoring card.

    The UPS is equipped with an SNMP slot to realize the UPS remote monitoring function, with functions such as automatic alarm, UPS operation status and fault prediction and diagnosis, and operation time control.

    Output RS-232 and RELAY signal for computer system connection, support Windows 95/98/2000 / NT / ME / XP, NOVELL / SNMP / ASMP /LINUX and other software

    ?


    TD31 6KVA detailed parameter table

    Rated Capacity6KVA/5.4KW
    modelTD11 6K

    TD31 6KVA input parameters

    Rectifier typeIGBT rectification
    Rated voltage380V (line voltage)
    Input voltage range304~478VAC
    Input frequency range46Hz~64Hz (adjustable)
    Input power factor>=0.99

    TD31 6KVA output parameters

    Rated output power6KVA/5.4KW
    Rated output voltage200/208/220/230/240VAC phase voltage
    The output voltageSynchronize with mains (mains mode); 50Hz ± 0.2% (battery mode)
    Way of workingOnline
    Output waveformSine wave
    Conversion time0ms
    Overload capacityWhen 105%±5%≤load, overload is pre-warned; when 105%±5%<load≤125%5%, transfer to bypass output after 2 minutes; 125%±5%<load≤150%±5%, 30 minutes Turn to bypass output later; when load >150%±5%, turn to bypass output after 500 milliseconds

    TD31 6KVA battery and running time

    battery modelMaintenance-free sealed lead-acid battery
    Standard machine backup time30 minutes to 8 hours optional
    Battery pack model-
    Typical battery charging time8 hours
    battery voltage192VDC

    TD31 6KVA system parameters and standards

    Installation methodTower
    Overall efficiencyUp to 90%
    Electromagnetic CompatibilityGB4943-2001/IEC62040-1
    Surge protectionIEC 61000-4-2.4.5 Level IV, IEC61000-4-3 Level III
    Protection typeIP20

    TD31 6KVA communication and management

    Interface portRS232, optional Wedpower card, AS400 card
    control panelLCD+LED status indication
    Audible alarmAlarm once every 4 seconds when mains power fails: special low battery alarm once every second

    TD31 6KVA physical index

    W260.00 mm
    D560.00 mm
    H717.00 mm
    weight58.00 KG
    colorblack

    TD31 6KVA  environment

    working environment0 - 40 °C
    Relative humidity0 - 95%
    Operating height0-1500 meters
    storage temperature-5 - 45 °C
    Storage relative humidity0 - 95%
    Storage height0-1500 meters
    Audible noise at 1 m from the surface of the device<50.00 dB

    TD31 6KVA warranty

    Standard warrantyRepair or replace within 3 years







    6KVA AC 220V input: AC 220V output

    Input parameters
    Input voltage220V AC (Single phase double wire)
    Enter the live wire diameter6mm2 (Square millimeter)
    Input zero wire diameter6mm2(Square millimeter)
    Input ground wire diameter6mm2(Square millimeter)
    Input air switch32A -1P (AC open) 
    Output parameters
    The output voltage220V AC (Single phase double wire)
    Output wire diameter6mm2(Square millimeter)
    Output neutral wire diameter6mm2(Square millimeter)
    Output ground wire diameter6mm2(Square millimeter)
    Output MCB32A -1P (AC open) 
    Battery parameters
    External battery MCB30A-2P (DC MCB)
    External battery wire diameter6mm2(Square millimeter)




    Backup model: One year warranty, one year warranty for built-in battery


    Online models: three-year warranty


    12V24AH capacity battery products: three-year warranty


    After-sales service contact information throughout the country: Contact us


    7*24 hours service telephone: 400-055-8433


    related product recommendation